ORDINANCE # 1949
AN ORDINANCE TO BEPEAED THE FIRE PREVENTION CODE
FOR THE CITY OF PRICHARD, ALABAMA
Sponsored by: MAYOR RON DAVIS
An Ordinance of the City of Prichard adopting the 2003 Edition of the International Fire
Code regulating and governing the safeguarding of Life and Property from fire and explosion hazards
arising from the storage, handling and use of hazardous substances, materials and devices and from
conditions hazardous to life or property in the occupancy of buildings and premises as herein
provided; providing for the issuance of permits and collection of fees therefor; repealing Ordinance
No. 1889 adopted February 8, 2001, 1997 adoption of the Standard Fire Preverition Code, and the
1997 National Fire Code of the City of Prichard, and all other ordinances in conflict therewith.
THE CITY COUNCIL OF PRICHARD, ALABAMA does oidain as follows:
SECTION ONE:
That certain document, a copy of which is on file in the office of the City Clerk of the City
of Prichard, Alabama, being marked and designated as the International Fire Code, 2003 Edition
(as published by the International Code Council, Inc., and copyrighted in December, 2002), including
Appendices B through G, inclusive, thereof, which is hereby incorporated by reference as a part of
this Ordinance as though fully set forth herein, is hereby adopted as the “Fire Code of the City of
Prichard” (sometimes hereinafter called “Fire Code”), regulating and governing the safeguarding of
life and property from fire and explosion hazards arising from the storage, handling and use of
Page 2
hazardous substances, materials and devices, and from conditions hazardous to life or property in
occupancy of buildings and premises as therein provided; providing for the issuance of permits and
collection of fees therefor; and each and all of the regulations, provisions, penalties, conditions and
terms of said Fire Code with the additions, insertions, deletions and changes, if any, prescribed in
the following sections of this Ordinance.
SECTION TWO:
Chapter 1, Section 102 of the Fire Code is hereby amended to read as follows:
Section 102.6. Referenced Codes and Standards. The
Codes and Standards referenced in this Code shall be those that are
listed in Chapter 45 and such Codes and Standards, as the same may
be revised or amended from time to time, shall be considered part
of the requirements of this Code to the prescribed extent of each
such reference. Where differences occur between the revisions of
This Code and the referenced Standards, the provisions of this Code
shall apply.
SECTION THREE:
Section 103 of the Fire Code adopted is hereby amended to add the following:
Section 103.1. Fire Department. The person in charge
shall be known in this Code as the Fire Official, who shall be called
the Fire Chief of the City of Prichard, and whois charged with the
implementation, administration and enforcement of the City of
Prichard’s Fire Code.
SECTION FOUR:
There is hereby added to Section 105.4 of said Fire Code the following new section
105.4.7:
105.4. Plan Review Fee.
Page 3
105.4.7.1. Standard Commercial Fee For each standard
© commercial construction project involving a set of drawings for a
single story structure of less than 15,000 square feet, a plans review
fee of $85.00 will be charged. This fee will include the charge for
reviewing one revised or corrected submittal(with clouded revisions).
Any third submittal and any subsequent submittals on the same
project shall be charged an additional $85.00 each.
105.4.7.2. Other Commercial Fee. For each commercial
construction project involving a set of drawings for a single story
structure containing 15,000 square feet or more, multi-story
structures, large assembly occupancies or shopping centers, the fee
charged for reviewing said plans is $170.00. This would include
review of one revised or corrected submittal (with clouded revisions).
Any third submittal and any subsequent submittals on the same
project would be charged an additional $85.00 each.
105.4.7.3. All commercial construction plans submitted for review
shall be stamped and signed by an Alabama registered architect or
engineer.
O SECTION FIVE:
Chapter 1, Section 105.6 of the Fire Code is hereby amended to read, in its entirety, as
follows:
105.6. Permits by Use. The Fire Official is authorized to
issue permits as set forth in Section 105.6.1 through 105.6.17.15,
hereinbelow.
105.6.1. Automatic Fire Sprinkler Systems.
105.6.1.1. No person shall install, modify or repair an
Automatic Fire Sprinkler System without first obtaining a permit
from the Bureau of Fire Prevention.
105.6.1.2. Any persons who installs Fire Sprinkler Systems
(hereinafter called in this Section 105.6 “installer”) must be certified
by the State Fire Marshall’s office and approved by the Fire Official
on an annual basis renewable in January of each year.
Page 4
105.6.1.3. Installer must have sprinkler plans approved by
the Fire Official before commencing any part of the installation.
105.6.1.4._ No company shall perform maintenance or
testing on any fire sprinkler system unless a representative of said
company is certified by the State Fire Marshal’s office and approved
by the Fire Official.
105.6.1.5. Upon final inspection, the NFPA Contractor’s
Material and Test Certificate for Aboveground Piping shall be
properly completed and submitted to the Fire Official.
105.6.1.6. The Fire Official shall require certain operational
tests upon final inspection.
105.6.1.7. The permit for each new installation, relocating
or replacing twenty-five (25) or more sprinkler heads shall cost One
Hundred Twenty-Five Dollars ($125.00) plus One Dollar ($1.00)
for each sprinkler head installed, relocated or replaced. Buildings
over three (3) stories in height shall require an additional Twenty ~
Five Dollars ($25.00) per floor for every floor above the third floor.
105.6.1.8. Relocating , replacing or installing more than
three (3) and fewer than twenty - five (25) sprinkler heads on an
existing system requires a permit from the Bureau of Fire Prevention.
The permit shall cost Eighty-Five Dollars ($85.00).
105.6.1.9. Repairs to an existing sprinkler system require a
permit. The permit to replace piping that affects more than three (3)
sprinkler heads shall cost Eighty-Five Dollars ($85.00).
105.6.2. Underground Piping for Fire Protection
Systems.
105.6.2.1. Any person who installs underground piping for
any fire protection system (hereinafter called in this Section 105.6.2.
installer”) must be approved by the Fire Official on an annual basis
renewable in January of each year.
105.6.2.2. No person shall install underground piping for
any fire protection system without first obtaining a permit. The
permit for each installation shall be Two Hundred Dollars ($200.00).
Page 5
105.6.2.3. Upon final inspection , the NFPA Contractor’s
Material and Test Certificate for Underground Piping shall be
properly completed and submitted to the Fire Official.
105.6.2.4. The Fire Official shall require certain operational
tests upon final inspection.
105.6.3. Standpipe Systems.
105.6.3.1. Any person who installs a Standpipe System
(hereinafter called in this Section 105.6.3. “installer” ) must be
certified by the State Fire Marshal’s office and approved by the Fire
Official.
105.6.3.2. No person shall install a Standpipe System
without first obtaining a permit from the Bureau of Fire Prevention.
The permit for each installation shall be One Hundred Dollars
($100.00) Plus Five Dollars ($5.00) for each hose connection,
105.6.3.3. The Fire Official shall require certain operational
tests upon final inspection.
105.6.4. Fire Pumps.
105.6.4.1. Any person who installs, repairs or services fire
pumps (hereinafter called in this Section 105.6.4. “installer”) must
be.a licensed Alabama Sprinkler Contractor and be certified by the
State Fire Marshal’s office and approved by the Fire Official on an
annual basis renewable in January of each year.
105.6.4.2. No person shall install or repair (i.e., repairs-
anytime the pump itself is disassembled or parts of the pump
controller panel are being removed or replaced, a new certification
shall be required) a fire pump without first obtaining a permit from
the Bureau of Fire Prevention. The permit for each installation or
repair shall be One Hundred Dollars ($100.00).
105.6.4.3. All testing of fire pumps shall comply with
NFPA 25,
105.6.4.4. The Fire Official shall require certain operational
tests upon final inspection.
Page 6
105.6.5. Servicing Fire Alarm Systems.
105.6.5.1. No person shall engage in the business of
servicing fire alarm systems without first being approved by the
Fire Official on an annual basis renewable in January of each year.
105.6.5.2. No person shall be issued a permit to install,
modify, repair, test or service fire alarm systems who does not
possess a then-current manufacturer’s certification of training from
the manufacturer of the type equipment to be installed, modified,
repaired, tested or serviced, or be certified by the National Institute
of Certification in Engineering Technologies (NICET) fire alarm
certified- minimum level II.
105.6.5.3. Owners of buildings may perform maintenance
on their own systems as long as the individual who performs the
system maintenance possess a then - current certificate of training
issued by the manufacturer of that system’s equipment or be
NICET fire alarm certified- minimum level II.
105.6.5.4. The annual permit fee for servicing fire alarm
systems shall be Two Hundred Dollars ($200.00).
105.6.5.5. A service tag shall be required to be installed by
the permitted alarm servicing individual or company at the control
panel of each fire alarm system, stating the service company’s name,
address, phone number, name of the technician performing the
service, date, and the type of service performed.
105.6.6. Fire Alarm Systems Installation.
105.6.6.1. Any person who installs a fire alarm system
(hereafter called in this Section 105.6.6. “installer” ) must be
approved by the Fire Official on an annual basis renewable in
January of each year.
105.6.6.2. No person shall install, modify or repair a fire
alarm system without having the plans approved by the Fire Official
before commencing any part of the work. No person shall
commence working on a fire alarm system without first obtaining a
permit from the Bureau of Fire Prevention.
Page 7
There is excepted from the requirements of this Section 105.6.6.
installations in any building with single station detectors only.
105.6.6.3. Any person or entity who designs fire alarm
systems must possess written evidence from the manufacturer of the
equipment to be installed, certifying that the designer is qualified to
design fire alarm systems or be National Institute of Certification in
Engineering Technologies (NICET) fire alarm certified - minimum
level IIL.
105.6.6.4. No permit shall be issued pursuant to this Code
until after the qualified fire alarm system designer shall have
submitted to the Bureau of Fire Prevention written evidence of said
designer’s responsibility for the supervision of the installation of the
system to be installed.
105.6.6.5. Installer must possess written evidence from the
manufacturer of the equipment to be installed , certifying that the
installer is qualified to install such equipment or the installer must
be NICET fire alarm certified - minimum level IL.
105.6.6.6. Licensed electricians may pull wire, mount
ancillary equipment, and connect the main power to the control
panel aftera permit has been issued; but no one other than a
qualified fire alarm installer shall be allowed to make any other
connections inside the control panel.
105.6.6.7. A certified fire sprinkler installer may install
devices integral to the operation of the fire sprinkler system, but
shall not make any connection to the fire alarm system.
105.6.6.8. Only the permitted fire alarm company that has
been approved by the Bureau of Fire Prevention’s Fire Official
shall be authorized to certify a fire alarm system upon completion
of the installation.
105.6.6.9. Upon final inspection, the NFPA Fire Alarm
System Record of Completion form shall be properly submitted to
the Fire Official and a fire alarm system test shall be performed in
the presence of the Fire Official.
105.6.6.10. The replacement and/or relocation of a control
panel constitutes an installation which requires a permit under this
Page 8
Section 105.6.6.
105.6.6.11. The permit for each installation shall cost One
Hundred Twenty-Five Dollars ($125.00) plus One Dollar ($1.00)
for each notification device and/or initiating device installed.
Buildings over three (3) stories in height shall require an additional
Twenty-Five Dollars ($25.00) per floor for every floor above the
third floor. If relocating, replacing or installing twenty-give (25) or
more devices, the above fee schedule applies.
105.6.6.12. Relocating, replacing or installing more than
three (3) and less than twenty-five (25) notification and/or initiating
devices on an existing system shall require a permit. The permit for
the installation and/or relocation of more than three (3) and less
than twenty-five (25) notification and/or initiating devices shall be
Eighty-Five Dollars ($85.00),
105.6.6.13. Repairs on an existing system shall require a
permit.
105.6.6.13.1. Repairs affecting an existing system with
more than three (3) and less than twenty - five (25) notification
devices and/or initiating devices shall require a permit. The permit
for the repairs on a system with more than three (3) and less than
twenty-five (25) notification and/or initiating devices shall be
Eighty-Five Dollars ($85.00).
105.6.6.13.2. Repairs affecting an existing system with
twenty - five (25) or more devices constitutes an installation
requiring a permit. The permit for each installation shall cost One
Hundred Twenty-Five Dollars ($125.00) plus One Dollar ($1.00)
for each notification device and/or initiating device installed.
Buildings over three (3) stories in height shall require an additional
Twenty-Five Dollars ($25.00) per floor for every floor above the
third floor.
105.6.6.14. All fire alarm circuit disconnecting means shall
have a red marking and shall be identified as “Fire Alarm”.
105.6.6.15. All fire alarm wiring junction boxes shall have
the cover painted red.
105.6.7. Portable Fire Extinguisher Service.
Page 9
105.6.7.1. No person shall engage in the business of
servicing portable fire extinguishers without first being approved by
the Fire Official on an annual basis, renewable in January of each
calendar year.
105.6.7.2. No person shall be issued a permit to service
portable fire extinguishers who does not possess a then - current
manufacturer ’s certification of training for servicing the type
extinguisher being installed or serviced.
105.6.7.3. The technician who actually performs the work
of servicing portable fire extinguishers shall sign and date the
service tag verifying that all work was done in compliance with
NEPA standards.
105.6.7.4. The annual permit for servicing portable fire
extinguishers shall be Two Hundred Dollars ($200.00).
105.6.8. Servicing Fixed Fire Extinguishing Systems.
105.6.8.1. No person shall engage in the business of
servicing and/or installing fixed fire extinguishing systems without
first being approved by the Bureau of Fire Prevention’s Fire
Official on an annual basis, renewable in January of each calendar
year.
105.6.8.2. No person shall be issued a permit to service or
install fixed fire extinguishing systems who does not possess a then-
current manufacturer’s certification of training for servicing and/or
installing the type system to be serviced or installed.
105.6.8.3. The technician who actually performs the work
of servicing fixed fire extinguishing systems shall sign and date the
service tag verifying that all work was done in compliance with
NFPA standards.
105.6.8.4. The annual permit to service fixed fire
extinguishing systems shall be Two Hundred Dollars ($200.00).
105.6.9. Fixed Fire Extinguishing Systems Installation.
105.6.9.1. No person shall be issued a permit to install a
fixed fire extinguishing system who does not possess a then-current
Page 10
manufacturer’s certification of training for installation of the type
system to be installed.
105.6.9.2. No person shall install a fixed fire extinguishing
system without first having plans approved and obtaining a permit
from the Bureau of Fire Prevention.
105.6.9.3. The permit for each system installed shail cost
One Hundred Twenty-Five Dollars ($125.00).
105.6.9.4. The Fire Official shall require certain
operational tests upon final inspection.
105.6.10 Installation of Stationary Aboveground
Flammable or Combustible Liquid Storage Tanks (AST).
105.6.10.1. No person shall install any stationary
aboveground flammable or combustible liquid storage tank without
first obtaining a permit from the Bureau of Fire Prevention.
105.6.10.2. No person shall be issued a permit until plans
showing the complete fueling system have been submitted to the
Fire Official for approval. Plans should include the relationship of
the AST to the property lines, buildings, public ways, other tanks,
and to the dispenser. The plans also shall show and list all the
safety devices to be installed on the tank.
105.6.10.3. The installation shall follow recognized
industry standards for aboveground tanks and the requirements of
NFPA 30 and NFPA 30A.
105.6.10.4. The permit fee for each new installation of an
aboveground flammable or combustible liquid storage tank to be
Installed is Fifty Dollars ($50.00).
105.6.11. Installation of Underground Flammable or
Combustible Liquid Storage Tanks.
105.6.11.1. No person shall install any underground
flammable or combustible liquid storage tank without first
obtaining a permit from the Bureau of Fire Prevention.
10
Page 11
105.6.11.2. Any person who installs underground
flammable or combustible liquid storage tanks (hereinafter called
in this Section 105.6.12. “installer” ) shall call for an inspection
prior to covering the tank or piping.
105.6.11.3. Installer shall call for a final inspection after
completing the installation. The Fire Official shall require certain
operational tests upon final inspection.
105.6.11.4. All underground flammable or combustible
liquid tanks shall be properly equipped with approved tie-downs to
prevent the tank from floating up.
105.6.11.5. The permit fee for each tank to be installed is
Two Hundred Fifty Dollars ($250.00).
105.6.12. Aboveground Storage Tanks (AST) for
Flammable or Combustible Liquids in Excess of 60 Gallons.
105.6.12.1. An annual permit for all aboveground
flammable or combustible liquids storage tanks (AST), whether
called portable or stationary, is required. The installation shall
follow recognized industry standards for aboveground tanks and
the requirements of NFPA 30 and NFPA 30A.
105.6.12.1.1. Gasoline. An AST in excess of 60 gallons
and less than 1,000 gallons capacity must also meet the following
requirements:
. tank must be listed for aboveground use;
. 110/120 volt AC or 12 volt DC, UL approved explosive-
proof dispenser may be mounted directly into bung opening
of tank;
. tank location shall be in accordance with NFPA 30A;
. tank must be equipped with normal venting and shall not
terminate under an eave or roof. Vent must termination 12
foot above grade;
. tank must be equipped with an emergency relief vent;
. tank must be safeguarded against vandalism, collision,
spillage, and overfill;
. the product name “GASOLINE- NO SMOKING IN
AREA-STOP MOTOR” shall be posted on tank or dike
wall;
11
Page 12
. contents shall not be dispensed by gravity and means shall
be provided to prevent the release of liquid by siphon flow;
, all piping shall be protected from physical damage.
105.6,12.1.2. Diesel. An AST in excess of 60 gallons and
less than 1,000 gallons capacity must also must also meet the
following requirements:
. tank must be listed for aboveground use;
. 110/120 volt AC or 12 volt DC, UL approved explosive-
proof dispenser may be mounted directly into bung opening
of tank;
. tank location- minimum distance to property line that may
or can be built upon 15 feet, public way 5 feet, important
building 5 feet;
. tank must be equipped with normal venting;
5 . tank must be equipped with an emergency relief vent;
e tank must be safeguarded against vandalism, collision,
spillage, and overfill;
. the product name “DIESEL- NO SMOKING IN AREA-
STOP MOTOR” shall be posted on tank or dike wall;
. contents shall not be dispensed by gravity and means shall
be provided to prevent the release of liquid by siphon flow;
. all piping shall be protected from physical damage.
***Exception: Tanks used for storage of Class IIIB combustible
liquids (crankcase draining).
105.6.12.2. It shall be unlawful for anyone to fill or
dispense from a flammable or combustible liquids storage tank that
does not have displayed a then - current annual inspection sticker
from the Bureau of Fire Prevention.
105.6.12.3. The annual permit fee for such tanks shall be
as follows:
Storage tank capacity.
Minimum (gallons)
Permit Amount
1,001 6,000 $115.00
12
Maximum (gallons)
Page 13
Minimum (gallons) Permit Amount
6,001 12,000 $150.00
12,001 50,000 $200.00
Over 50,000 | 8250.00
105.6.13. Decommissioning of Flammable or
Combustible Liquid Storage Tanks.
Maximum (gallons)
105.6.13.1. No person shall decommission any flammable
or combustible liquid storage tank without first obtaining a permit
from the Bureau of Fire Prevention.
105.6.13.2. The fee for each permit shall be One Hundred
Dollars ($100.00). A permit is required for each tank.
105.6.13.3. The Fire Official shall require verification of
inerting and a written statement of method used prior to issuing a
permit.
105.6.14. Open Burning.
105.6.14.1. In order to promote public health, safety, and
welfare, no person shall be permitted to kindle or maintain any
bonfire, or to authorize any such fire to be kindled or maintained,
except by obtaining a permit from the Bureau of Fire Prevention’s
Fire Official.
***Exception: Recreational fire (as defined in Section 302).
105.6.14.2. In order to promote public health, safety and
welfare, no person shall be permitted to kindle or maintain any
rubbish fire, or to authorize any such fire to be kindled or
maintained, except by obtaining a permit from the Fire Official.
The fee for each burn permit shall be Five Hundred Dollars
($500.00).
105.6.14.3. Any person who applies for a burn permit
from the Bureau of Fire Prevention must possess a City of Prichard
business license and liability insurance. No burn permit shall be
O 3
Page 14
issued to anyone who has not produced written evidence of a
liability insurance policy in the amount of not less than One
Million Dollars ($1,000,000.00) which such policy shall list the
City of Prichard as being additionally insured and the Bureau of
Fire Prevention as the certificate holder.
***Exception: Property owner shall not be required to have a
business license but shall be required to have the liability insurance
coverage as above.
105.6.15. Special Amusement Event.
105.6.15.1. A permit shall be required to operate a special
amusement event and shall apply to any temporary operations such
as Haunted Houses, Ghost Walks, or other similar operations
where combustible decorative material, confusing sounds and/or
visual effects are present.
105.6.15.2, Any person who applies for a special
amusement permit from the Bureau of Fire Prevention must possess
a City of Prichard business license and liability insurance. No
permit shall be issued to anyone who has not produced written
evidence of a liability insurance policy in the amount of not less
than One Million Dollars ($1,000,000.00) which such policy shall
list the Bureau of Fire Prevention as certificate holder and the City
of Prichard as being additionally insured.
105.6.15.3. Any person who applies for a special
amusement permit shall submit a written emergency planning and
preparedness plan. This plan shall address the issues in Chapter 4
of the International Fire Code.
105.6.15.4. The cost for a special amusement building
permit shall be Fifty Dollars ($50.00) unless otherwise stated
therein, each such special amusement building permit shall expire
on the thirty-first (31") calendar day after the date of issuance of
the same. .
105.6.15.5. The Fire Official shall require certain
operational tests upon final inspection prior to opening.
105.6.16. General Requirements.
14
Page 15
105.6.16.1. No permit shall be issued to any individual or
company who does not possess a then - current City of Prichard
business license related to the area of operation or business to be so
permitted,
105.6.16.2. No permit shall be issued to any individual or
company who does not possess a then-current Certificate of
Liability Insurance in the amount of One Million Dollars
($1,000,000.00) and list the City of Prichard Bureau of Fire
Prevention as the certificate holder. Sprinkler contractors shall
also have Errors & Omissions and/or Professional Liability
Coverage Endorsement on the insurance certificate.
105.6.16.3. It shall be required that a copy of all annual or
semi-annual inspection reports be submitted to the Bureau of Fire
Prevention with any and all deficiencies clearly noted.
105.6.16.4. No person or company shall be issued a permit
under this Code until such time as they show proof of then- current
certification of training and be approved by the Fire Official.
105.6.16.5. Violation/Penalties. Where work for which a
permit is required by this Code commences prior to obtaining said
permit, the permit fee herein specified shall be doubled.
105.6.16.6. Re-Inspection fee(s). A fee of Fifty Dollars
($50.00) shall be paid for each re-inspection requested or required.
105.6.16.7. Each letter of inspection or copy of an official
inspection report shall cost Fifty Dollars ($50.00).
105.6.16.8. Emergency Repairs. Where equipment
replacement and/or repairs must be performed in an emergency
situation, the permit application shall be submitted within the next
business day at the Fire Official’s office.
105.6.16.9. Weekend and emergency inspections shall
cost $50.00 for the first (1") hour and $25.00 for each additional
hour.
105.6.16.10. Prichard Fire - Rescue Department, Bureau
of Fire Prevention mailing address is 303 W. Turner Rd. Prichard,
Alabama 36610.
15
Page 16
105.6.16.11. Payment. All checks and money orders shall
be made out to the Prichard Fire-Rescue Department.
105.6.16.12. In addition to all other fees or charges
specified herein above in this Ordinance, the fee for each permit
issued pursuant to this Section shall be increased by One Dollar
($1.00) processing fee. This fee to be collected to purchase
updated computers and software for the Bureau of Fire Prevention.
105.6.16.13. All installation permits shall automatically
expire 180 days from the date of issuance.
105.6.16.14. Permits are not transferable and any change
in occupancy, operation, tenancy or ownership shall require that a
new permit be issued.
105.6.16.15. All private fire hydrants shall be color-coded
in accordance with NFPA 291 Guidelines, with these additional
requirements:
. Marking on private hydrants- they shall be painted light
gray, and all discharge caps shall be painted according to
the Class-rated capacity of the hydrant to distinguish them
from public hydrants.
. All private hydrants shall have a control valve located and
clearly marked near the hydrant.
. A blue marker shall be placed in the street for rapid
identification at night.
105.6.16.16. Acopy of the permit and approved plans
shall be on the job site.
SECTION SIX:
Chapter 1, Section 108 of the Fire Code is hereby amended to read, in its entirety, as
follows:
108.1. Board of Appeals established. In order to hear
and decide appeals of orders, decisions or determinations made by
the Fire Official relative to the application and interpretation of
this Code, there shall be and is hereby created a Board of Appeals
composed of the five (5) members to be appointed by the Mayor.
The Fire Official shall be an ex officio member of said Board but
16
Page 17
shall have no vote on any matter before the Board. The Board
may adopt rules of procedure for conducting its business, and shall
render all decisions and findings in writing to the appellant with a
duplicate copy to the Fire Official.
108.2, Limitations on authority. An application for
appeal shall be based on a claim that the intent of this Code or the
tules legally adopted hereunder have been incorrectly interpreted,
the provisions of this Code do not fully apply, or an equivalent
method of protection or safety is proposed. The Board shall have
no authority to waive any requirements of this Code.
108.3. Appeals
108.3.1. General. Whenever it is claimed that the
provisions of this Code do not apply, or when the Fire Official
shall reject an alternate material method of construction, or when
it is claimed that the true intent and meaning of this Code or any
of the regulations hereunder has been misconstrued or incorrectly
interpreted, the owner of such building or structure, or his duly
authorized agent, may appeal the decision of the Fire Official to
the Board of Appeals. Notice of such appeal shall be in writing
and filed within fifteen (15) days after the decision is rendered by
the Fire Official. Appeals shall be on forms provided by the Fire
Official. Notice of appeal shall be filed with both the office of the
City Clerk and with the Fire Chief of the City of Prichard.
108.3.2. Unsafe or Dangerous Building. In case of a
building, structure or operation which, in the opinion of the Fire
Official, is unsafe or dangerous, the Fire Official may, in his order,
limit the time for such appeal to a shorter period.
108.3.3. Variances. Every decision of the Board of
Appeals shall be final, subject, however, to such remedy as an
aggrieved party may have at law or in equity. Every decision of
the Board of Appeals shall be in writing and shall indicate the vote
upon the decision. Every decision of the Board of Appeals shall
be properly filed in the office of the City Clerk and shall be open
to public inspection; a copy shall be sent to the Fire Chief of the
City of Prichard, a copy shall be sent to the appellant by U.S.
Certified Mail, return receipt requested, at the address
provided for the appellant in said appellant’s notice of appeal;
and a copy shall be kept publicly posted in the office of the City
17
Page 18
Clerk for a period of two (2) weeks after the filing.
108.3.4. Action. The Board of Appeals shall, in every
case, reach a decision without unreasonable or unnecessary delay.
108.3.5. Decision is Final. Ifa decision of the Board of
Appeals reverses or modifies a refusal, order or disallowance of
the Fire Official, or varies the application of any provision of this
Code, the Fire Official shall immediately take action in accordance
with such decision.
SECTION SEVEN:
Chapter 1, Section 109 of the Fire Code is hereby amended to read as follows:
109.3. Violation Penalties. Persons who shall violate a
provision of this Code or shail fail to comply with any of the
‘requirements thereof or who shall erect, install, alter, repair or do
‘work in violation of the approved construction documents or
directive of the Fire Code Official, or of a permit or certificate
used under provisions of this Code, shall be guilty of a
misdemeanor offense against the City, punishable by a fine of not
QO more than Five Hundred Dollars ($500.00), or imprisonment not
exceeding 180 days, or both such fine and imprisonment. Each
day that a violation continues after Due notice has been served
shall be deemed a separate offense.
SECTION EIGHT:
Chapter 22, Section 2204.3 of the Fire Code is hereby amended to read, in its entirety, as
follows:
2204.3. Unattended Self - Service Motor Fuel
Dispensing Facilities. Unattended self - service motor fuel
dispensing facilities that are open to the public shall not be
allowed.
SECTION NINE:
Page 19
O
This Ordinance shall be in full force and effect on and after the 3rd day of
January > 2007, and all ordinances heretofore adopted by the City of Prichard in
conflict herewith are hereby repealed.
SECTION TEN:
If any section, sentence, paragraph, clause, phrase or word of this Ordinance is, for any
reason, held or declared to be unconstitutional, inoperative or void, such holding or declaration shall
not affect the remaining portions of this Ordinance, and it shall be construed to have been the intent
of the City Council of the City of Prichard to pass this Ordinance without such unconstitutional,
invalid or inoperative part therein, and the remainder of this Ordinance shall be deemed and held to
be valid as if'such part of parts had not been included therein.
SECTION ELEVEN:
A copy of this Ordinance shall be published pursuant and according to law, after
its adoption, but it shall not be necessary for the said International Fire Code to be published in a
newspaper, nor shall the same be spread at length upon the minutes of this Council, but this
Ordinance shall be recorded in the Minutes.
19
Page 20
C \ ADOPTED this the _3rd_ day of January, 2008.